Interlock Defeat


Ion sources and injection BL

EGUN:BIAS and EGUN turbine warn/trip alarm levels
Implementation: Number:
2024-05-28 14:00:00 2024-277

Brandon Humphries

Removed
Estimated Duration:
20 weeks

The replacement RUG3 for the EGUN turbine has an offset of about 0.5 V compared to the previous one. So the interlock and alarms (warn/trip) needed to be lowered by 0.5 V until a new RUG3 is obtained. Warn level lowered from 22.5 V to 22.0 V and trip level lowered from 22.0 V to 21.5 V.

2

1- ERSS panel blue box


1- Cork board in back of DCR

Changes were implemented through the PLC by Controls (alarms are filtered through a secondary signal).

Protection still exists, just with the offset corrected. System expert (Marco) approved the change.

16934

A2024-05-28-2