Interlock Defeat / Device Disable
Management System v2.0 (Driver)
Accelerator Complex:



Home
List of Defeats   ▸
List of Disables ▸
Fill Out a Defeat
Fill Out a Disable
Add/Modify User
Add/Modify System
Login
Help
Implementation Removal

Interlock Defeat


Targets

STF BYP-001 Pinned: Water Jacket Low-High Level
Implementation: Number:
2024-06-16 18:40:00 2024-320

David Bandiera

Removed
Estimated Duration:
1 weeks

Low-High Level sensor in the STF Water Column is showing Not OK and tripping the beam. The Water Jacket level is not changing and has been stable for days. OK'd by Yetvart after discussion.

2

1) Rear of Rack 1-A on SAB2



2) DCR Defeat Board

Pin placed in STF Defeat Board signal BYP-001 at the rear of Rack 1-A on SAB2.

Other STF Water Jacket level sensors are active, in particular the Low-Low level sensor is active. Water Jacket level being actively monitored in DCR

17073