Interlock Defeat /
Device Disable
Management System
v2.0
(Driver)
Accelerator Complex:
Driver
RIB
TR13
☰
Ops Apps Page
3DB
Webplan
Home
List of Defeats ▸
All
Active
Unacked
List of Disables ▸
All
Active
Unacked
Fill Out a Defeat
Fill Out a Disable
Add/Modify User
Add/Modify System
Login
Help
Implementation
Removal
Interlock Defeat
System(s) Affected:
Targets
Interlock to be Defeated:
STF BYP-001 Pinned: Water Jacket Low-High Level
Implementation:
Number:
Date:
2024-08-07
Time:
21:06:00
2024-397
Implemented By:
David Bandiera
In Consultation With:
Status:
Removed
Estimated Duration:
1 weeks
Reason for Defeat:
Low-High Level sensor in the STF Water Column is showing Not OK and tripping the beam. The Water Jacket level is not changing and is stable. OK'd by Louis after discussion.
Number of Yellow Tags:
2
Location of Defeat Tag(s):
1) DCR Defeat Board
2) SAB2 Rack 1-A
How Was Defeat Implemented?
Where is Defeat Located?:
Pin placed in STF Defeat Board signal BYP-001 at the rear of Rack 1-A on SAB2.
Describe Alternate Protection:
Other STF Water Jacket level sensors are active, in particular the Low-Low level sensor is active. Water Jacket level being actively monitored in DCR
Fault Reports:
Work Permits:
Disables:
Interlock Defeat
Removal:
Number:
Date:
2024-12-05
Time:
14:51:00
2024-397
Removed by:
David Bandiera
Status:
Removed
Interlock Verification Method:
Water level stable in the water column. Pin removed from STF BYP 005 and no trip.
Number of Tags Removed:
2
Comments:
Brandon Humphries
David Bandiera
Elena Bylinskaia
Jason Wait
Sierra Dean
Robert Scheepmaker
Eric Chapman
Ryan Lovelidge
Riley Schick-Martin
Dale Nagra
Travis Kurucz
Chris Sooley
Kevin Lucow
Jas Uppal
Kathleen Genge
Gauhar Hayat
Frank Hosta
Ryan Anderson