Implementation Removal

Interlock Defeat


Targets

STF BYP-001 Pinned: Water Jacket Low-High Level
Implementation: Number:
2024-08-07 21:06:00 2024-397

David Bandiera

Removed
Estimated Duration:
1 weeks

Low-High Level sensor in the STF Water Column is showing Not OK and tripping the beam. The Water Jacket level is not changing and is stable. OK'd by Louis after discussion.

2

1) DCR Defeat Board


2) SAB2 Rack 1-A

Pin placed in STF Defeat Board signal BYP-001 at the rear of Rack 1-A on SAB2.

Other STF Water Jacket level sensors are active, in particular the Low-Low level sensor is active. Water Jacket level being actively monitored in DCR