Implementation Removal

Interlock Defeat


Services

Beam dump water flow signal smoothing increased to 0.95
Implementation: Number:
2024-12-11 13:00:00 2024-552

Brandon Humphries

Active
Estimated Duration:
4 weeks

Noise started on the beam dump water flow signal (EWS:HAW:FG02) on Dec 10. The noise spikes were causing trips of the EHD run permit and preventing beam tests. Signal smoothing increased from 0.8 to 0.95 to help smooth out the large spikes.

2

1- On cork board in back of DCR


1- On safety system box on E-LINAC side of the DCR

Ricky (Controls) changed the smoothing in the Control system code.

Protections are still in place, they will just be a little slower. This was approved by Thomas Planche.

17595




Brandon Humphries: 2024-12-12 15:20:44.68821
Smoothing was increased further to 0.99 after another alarm/trip was received yesterday (see e-log https://web.accel.triumf.ca/elinac_elog/Elog_show_result.pl?inid=57952&style=thread&timemode=eventtime).