Interlock Defeat


Ion sources and injection BL

Cryo 165 gate valve temperature interlock
Implementation: Number:
2023-09-13 22:30:00 2023-509

Eric Chapman

Removed
Estimated Duration:
1 weeks

Poor ISIS vacuum trips machine on ISIS beam loss, pumping required to maintain beam delivery. Cryo 165 cold head above trip threshold auto closing gate valve.

1

DCR defeats.

VIB EPICS window for IB:GV165CYP. "IB:CCYP147 temp ok" interlock bypassed in EPICs

Manually close gate valve if vacuum degrades too far in ISIS beamline due to cryopump out gassing. Strips running on CYCCON09 next to supervisor station.

16249




Eric Chapman: 2023-09-14 17:43:03.046778
Interlock defeated is "IB:CCYP165 temp ok" in epics, disregard error above.
Kevin Lucow: 2023-09-15 14:20:03.337549
Defeat reviewed and OK'd by T. Stanford.