BL2C4 STF Supply Resistivity
Implementation: Number:
2023-10-12 16:45:00 2023-563

Kevin Lucow

Removed
Estimated Duration:
99 weeks

STF Supply Resistivity reads "PLCDat" error causing cyclotron trip. This is a known problem; see Fault 13917. This signal should be used as a diagnostic readback only, and not as an interlock.





*Do not remove this defeat until supply resistivity signal has been removed as a BL2C4 interlock.

2

1) MCR Defeat Board. 2) SAB2 rack 1A.

SAB2, rack 1A, BYP-043.

STF Return Resistivity and other STF interlocks active.

16358, 13917