Interlock Defeat / Device Disable
Management System v1.5 (Driver)

Accelerator Complex:



Home
List of Defeats   ▸
List of Disables ▸
Fill Out a Defeat
Fill Out a Disable
Add/Modify User
Add/Modify System
Login
Help
Implementation Removal

Interlock Defeat


Ion sources and injection BL

Cryo 165 gate valve temperature interlock
Implementation: Number:
2023-11-19 09:30:00 2023-613

Eric Chapman

Removed
Estimated Duration:
1 weeks

Cryo 165 cold head above trip threshold auto closing gate valve. Cryo effectively pumping on the beamline despite being over temperature interlock value improving vacuum from 9e-7T to 3e-7T on IG155.

1

none

VIB EPICS window for IB:GV165CYP. "IB:CCYP165 temp ok" interlock bypassed in EPICs

Manually close gate valve if vacuum degrades too far in ISIS beamline due to cryopump out gassing. Strips running on CYCCON09 next to supervisor station.





Eric Chapman: 2023-11-19 09:27:52.531674
This cryopump has been stubborn for ISIS personnel. Despite their best efforts continues to act up. Last time it was given some gas load for a few hours, the cold head cooled off and the interlock cleared.