Implementation Removal

Interlock Defeat


Targets

STF byp-008 ion exchanger return flow
Implementation: Number:
2023-12-02 21:45:00 2023-636

Frank Hosta

Removed
Estimated Duration:
5 weeks

BYP-006 STF target cooling water flow signal noisy, dropping below trip warn sometimes. Approved by Steve Sapriken and Yetvart Hosepyan.

2

1) STF bypass cabinet on SAB2




2) MCR defeat board

BYP-006 pinned in SAB2 STF bypass cabinet.

Water pump indication still functions along with the target water level switches.

16552