Interlock Defeat
System(s) Affected:
Fire Alarm System
Interlock to be Defeated:
IAMI B1 and B2 sprinkler flow switches, Zone 1 and 2 test
Implementation:
Number:
Date:
2024-04-08
Time:
08:30:00
2024-175
Implemented By:
Eric Chapman
In Consultation With:
Status:
Removed
Estimated Duration:
9 hours
Reason for Defeat:
Demolish and Remove Sprinkler Lines in B2 Shell Space in IAMI.
Number of Yellow Tags:
1
Location of Defeat Tag(s):
DCR
How Was Defeat Implemented?
Where is Defeat Located?:
Zones 1 and 2 in test mode with Telus monitoring until 17:00. Flow switches 13-075-69/70/72/77 disabled on XL graphics.
Describe Alternate Protection:
Firewatch.
Fault Reports:
Work Permits:
M2024-03-25-1
Disables:
Interlock Defeat
Removal:
Number:
Date:
2024-04-08
Time:
17:30:00
2024-175
Removed by:
Ryan Anderson
Status:
Removed
Interlock Verification Method:
Devices had been rearmed via the FAS graphics panel earlier, as per comment. FAS zones brought back online at 17:00 by monitoring company.
Number of Tags Removed:
1
Comments:
Eric Chapman:
2024-04-08 12:27:18.242886
Devices re-armed. System remains in Zone 1 and 2 test as a supervisory is coming through on 13-075-069 Cyclotron B2 sprinkler Air.