Interlock Defeat / Device Disable
Management System v1.5 (Driver)

Accelerator Complex:



Home
List of Defeats   ▸
List of Disables ▸
Fill Out a Defeat
Fill Out a Disable
Add/Modify User
Add/Modify System
Login
Help
Implementation Removal

Interlock Defeat


Targets

T2 target water flow low warning/trip lowered
Implementation: Number:
2021-09-01 21:45:00 2021-294

Eric Chapman

Removed
Estimated Duration:
1 weeks

Numerous warnings tonight on T2 water flow. Warning value lowered to 3.0GPM from 3.2, Trip dropped to 2.8 from 3.0 in epics.

1

EPICS T2 water system cooling system thresholds page.

Warning value lowered to 3.0GPM from 3.2, Trip dropped to 2.8 from 3.0 in epics.

Trip and warn still functioning just lowered a bit to prevent nuisance warnings.